OMRON MY2N AC220-240

Product classification Monostable relays
Built-in LED indicator type
Coil ratings 220 VAC/240 VAC
Operating indicator LED
Contact type DPDT
Contact method Single
Contact material Ag
Contact rated load 220 VAC 5 A (Resistive load)
220 VAC 2 A (Inductive load (cos φ= 0.4))
24 VDC 5 A (Resistive load)
24 VDC 2 A (Inductive load (L/R = 7 ms))
Maximum switching voltage 250 VAC
125 VDC
Maximum switching current AC: 5 A
DC: 5 A
Failure rate 1 mA at 5 VDC (failure level: P Reference value) (Switching frequency of 120 operations per minute)
Ambient temperature (Operating) -55 to 60 ℃ (with no icing or condensation)
Ambient_humidity (Operating) 5 to 85%RH (with no icing or condensation)
Contact resistance 50 mΩ max., Measuring the voltage drop across the contacts by applying test voltage/current as 5 VDC 1 A
Release time (Reset time) 20 ms max. (The operate or release time was measured with the rated voltage at an ambient temperature of 23 ℃)
Insulation resistance Between coil and contacts: 100 MΩ min. (at 500 VDC)
Between contacts of different polarity: 100 MΩ min. (at 500 VDC)
Between contacts of same polarity: 100 MΩ min. (at 500 VDC)
Dielectric strength Between coil and contacts: 2000 VAC (50/60 Hz 1 min)
Between contacts of different polarity: 2000 VAC (50/60 Hz 1 min)
Between contacts of same polarity: 1000 VAC (50/60 Hz 1 min)
Vibration resistance (Destruction) 10 to 55 to 10 Hz, 0.5-mm single amplitude (1-mm double amplitude)
Vibration resistance (Malfunction) 10 to 55 to 10 Hz, 0.5-mm single amplitude (1-mm double amplitude)
Shock resistance (Destruction) 1000 m/s**2
Shock resistance (Malfunction) 200 m/s**2
Endurance (Mechanical) 50 million operations min. (switching frequency 18,000 operations/h)
Endurance (Electrical) 500,000 operations min. (23 ℃, Rated load, switching frequency 1,800 operations/h)
Protective structure Closed type (cover)
Terminal structure Plug-in terminal
Weight Approx. 35 g

XEM CATALOG SẢN PHẨM TẠI ĐÂY